闭式系统蒸汽管径推荐速度_闭式空调系统管径选用表
流速
管徑
15
20
25
32
40
50
70
80
100
125
150
200
250
300
350
400
m/s
內徑
15.8
21.3
27
35.8
41
53
68
80.5
106
125
150
207
259
309
357
404
W
0.18
0.32
0.52
0.9
1.19
1.99
3.27
4.51
7.94
11
15.9
30.3
47.4
67.5
90.1
115
R
2
11.1
7.4
5.4
3.7
3.1
2.2
1.6
1.3
0.9
0.7
0.6
0.4
0.3
0.2
0.2
0.2
W
0.21
0.38
0.62
1.08
1.43
2.38
3.92
5.5
9.53
13.3
19.1
36.4
56.9
81
108
138
R
2
14.5
10.3
7.5
5.1
4.3
3.1
2.2
1.8
1.3
1
0.8
0.5
0.4
0.3
0.3
0.2
W
0.25
0.45
0.72
1.26
1.66
2.78
4.58
6.41
11.1
15.5
22.3
42.4
66.4
94.5
126
162
R
2
20.4
13.6
9.9
6.8
5.7
4.1
3
2.4
1.7
1.4
1.1
0.7
0.5
0.4
0.4
0.3
W
0.28
0.51
0.82
1.45
1.9
3.18
5.23
7.33
12.7
17.7
25.5
48.5
75.9
108
144
185
R
2
26.1
17.4
12.6
8.9
7.3
5.2
3.8
3
2.1
1.7
1.4
0.9
0.7
0.6
0.5
0.4
W
0.32
0.57
0.93
1.63
2.14
3.57
5.88
8.25
14.3
19.9
28.6
54.5
85.4
121
126
208
R
2
32.4
21.7
15.7
10.9
9.1
6.5
4.7
3.8
2.7
2.2
1.7
1.2
0.9
0.7
0.6
0.5
W
0.35
0.64
1.03
1.81
2.38
3.97
6.54
9.16
15.9
22.1
31.8
60.6
94.8
134
150
231
R
2
39.4
26.3
19.1
13.2
11
7.9
5.7
4.6
3.3
2.6
2.1
1.4
1.1
0.9
0.7
0.6
W
0.39
0.7
1.13
1.99
2.61
4.37
7.19
10.1
17.5
24.3
35
66.6
104
148
196
254
R
2
47.1
31.5
22.9
15.8
13.2
9.5
6.9
5.5
3.9
3.2
2.5
1.7
1.3
1
0.9
0.7
W
0.42
0.77
1.24
2.17
2.85
4.77
7.84
11
19.1
26.5
36.2
72.7
114
162
216
277
R
2
55.4
37
26.9
18.6
15.5
11.1
8.1
6.5
4.6
3.7
3
2
1.5
1.2
1
0.9
W
0.46
0.83
1.34
2.35
3.09
5.16
8.5
11.9
20.7
28.7
41.4
78.8
123
175
234
300
R
2
64.5
43.1
31.3
21.6
18.1
12.9
9.4
7.6
5.3
4.3
3.4
2.3
1.7
1.4
1.2
1
W
0.49
0.89
1.44
2.53
3.33
5.56
9.15
12.8
22.2
30.9
44.5
84.8
133
189
252
323
R
2
74.1
49.5
36
24.9
20.8
14.9
10.5
8.7
6.1
5
4
2.7
2
1.6
1.4
1.2
W
0.53
0.96
1.55
2.71
3.56
5.96
9.81
13.7
23.8
33.1
47.7
90.9
142
202
270
346
R
2
84.5
54.4
41
28.3
23.7
17
12.3
9.9
7
5.7
4.5
3.1
2.3
1.8
1.5
1.3
W
0.56
1.02
1.65
2.89
3
6.35
10.5
14.7
25.4
35.3
50.9
96.9
152
216
288
369
R
2
95.5
63.1
46.4
32.1
24.8
19.2
13.9
11.2
7.9
6.4
5.1
3.4
2.6
2.1
1.7
1.5
W
0.6
1.09
1.75
3.07
4.04
6.75
11.1
15.6
27
37.6
54.1
103
161
229
306
392
R
2
107
71.6
52.1
36
30.1
21.6
15.6
12.6
8.9
7.2
5.7
3.8
2.9
2.3
2
1.7
W
0.63
1.15
1.86
3.25
4.28
7.15
11.8
16.5
28.6
39.8
57.3
109
171
243
324
415
R
2
120
79.9
58.1
40.1
33.5
24
17.4
14.1
9.9
8.1
6.4
4.3
3.2
2.6
2.2
1.9
W
0.67
1.21
1.96
3.43
4.52
7.55
12.4
17.4
30.2
42
60.4
115
180
256
342
438
R
2
133
88.6
64.4
44.5
37.2
26.7
19.4
15.6
11
8.9
7.1
4.8
3.6
2.9
2.4
2.1
W
0.7
1.28
2.06
3.61
4.75
7.94
13.1
18.3
31.8
44.2
63.6
121
190
270
340
462
R
2
146
97.7
71.1
49.1
41.1
29.4
21.4
17.2
12.1
9.9
7.8
5.2
4
3.2
2.7
2.3
W
1.34
2.16
3.79
4.99
8.34
13.7
19.2
33.3
46.4
66.8
127
199
283
378
485
R
2
107
78
53.9
45.1
32.3
23.5
18.9
13.3
10.8
8.6
5.8
4.4
3.5
2.7
2.5
W
1.4
2.27
3.98
5.23
8.74
14.4
20.2
35
48.6
70
133
209
297
396
508
R
2
117
85.3
59
49.3
35.3
25.6
20.7
14.6
11.8
9.4
6.3
4.8
3.8
3.2
2.8
W
2.37
4.16
5.47
9.13
15
21.1
36.5
50.8
73.2
139
218
310
414
531
R
2
92.9
64.2
53.7
38.5
27.9
22.5
15.9
12.9
10.3
6.9
5.2
4.2
3.5
3
W
2.47
4.34
5.7
9.53
15.7
22
38.1
53
76.3
145
227
374
432
554
R
2
101
69.7
58.3
41.8
30.3
24.4
17.2
14
11.1
7.5
5.6
4.3
3.8
3.3
W
4.52
5.94
9.93
16.3
22.9
39.7
55.2
79.5
151
237
337
450
577
R
2
75.5
63.1
45.2
32.8
26.5
18.7
15.2
12.1
8.1
6.1
4.9
4.1
3.5
W
4.7
6.18
10.3
17
23.8
41.3
57.4
82.7
158
247
351
468
600
R
2
81.4
68.1
48.8
35.4
28.5
20.1
16.3
13
8.7
6.6
5.3
4.4
3.8
W
6.42
10.7
17.7
24.7
42.9
59.6
85.9
164
256
364
486
623
R
2
73.2
52.5
38.1
30.7
21.7
17.6
14
9.4
7.1
5.7
4.8
4.1
W
6.65
11.1
18.3
25.7
44.5
61.9
89.1
170
266
372
505
646
R
2
78.6
56.3
40.9
32.9
23.2
18.9
15
10
7.6
6.1
5.1
4.4
1.25
1.3
1.35
1.4
1.05
1.1
1.15
1.2
0.85
0.9
0.95
1
0.65
0.7
0.75
0.8
0.45
0.5
0.55
0.6
0.25
0.3
0.35
0.4
總結
以上是生活随笔為你收集整理的闭式系统蒸汽管径推荐速度_闭式空调系统管径选用表的全部內容,希望文章能夠幫你解決所遇到的問題。
- 上一篇: 2021年做什么生意前景好 可以考虑这
- 下一篇: 装机优盘怎么复原 使用优盘进行系统恢复教